BAM Oven
Ignition Test for Airborne Dust (BAM Oven)
This test is designed to determine the ignition temperature of airborne dust on a hot surface (e.g. spray drier).
First the oven is heated up to 600°C. With the heater switched off and the oven temperature falling, the dust samples are blown into the oven by means of a rubber bulb, e.g. every 50°C.
Ignition is considered to have taken place, if the injected dust ignites or decomposes producing flames and/or explosion.
Contact
Swiss Institute for the Promotion of Safety and Security
Adrien Bisel, Phone +41 (0)61 696 55 99, Fax +41 (0)61 696 70 72
Information and Orders
Petra Meier, Phone +41 (0)61 696 57 24, Fax +41 (0)61 696 70 72
|